SIZE OF METER
The dimension of the meterhead should be selected on the basis of liquid flow, the smallest possible transmitter is selected for a given maximum flow rate. This will ensure optimal accuracy of measurement.
If the metering section is smaller than the pipework in the installation the connecting pieces should be tapered.
 
LOCATION OF TRANSMITTER
The transmitter should be located in the piping system so that the metering pipe is always filled with liquid as the transmitter can register flow even if the metering pipe is empty. As the transmitter sees air in the liquid as a volume, the volume of air in the liquid must be reduced to a minimum, and the transmitter should be located in the piping system, at the point of maximum pressure. Here the volume of the air is minimum hence the influence of air on the measurement will also be minimum. If the transmitter is located downstream of a pump which may suck air during the measuring period an air eliminator should be mounted upstream of the transmitter. The transmitter can be mounted both horizontally and vertically. Air elimination must always be guaranteed. The positive flow direction is indicated by an arrow on the meterhead.
 
 
To create the best conditions for precise metering a straight run of at least 3x D should be mounted up- stream and downstream of the transmitter. When selecting the location of the transmitter it must be ensured that the ambient temperature is kept within the specified limits. Finally, the transmitter should be located so that the electronic box and the terminal box can be dismantled and mounted on site.
The transmitter should always be electrically connected thus preventing condensation in the electronics.