BrandName: EPI KRAL GREYLINE EMCO KEM PROCES-DATA A/S Aliamag Electromagnetic Flowmeter
   
Flowmeter Series > Proces-Data A/S
 
 
OUTPUT SIGNALS
 
The transmitter has three outputs, OUTPUT 1, 2, and 3.

OUTPUT 1 is a power supply output, which can be used for power supply of external counter circuit. The voltage of the output can vary from 20 to 32 V DC.

OUTPUT 2 can be selected for one of three functions:
1: Pulse signal, 0-5 c/s. The signal is taken to a counter, electronic or electromechanical, for indication of the total volume, e.g. in litres.
2: Sign for OUTPUT 3. The signal indicates the flow direction and can be taken to an UP/DOWN counter, which is actuated by pulses from OUTPUT 3.
3: The output signal from the pre-set counter. Before start of measuring a SET-point via the display is inserted, and the pre-set counter is reset. When the required volume is achieved, OUTPUT 2 gives a stopsignal.

OUTPUT 3 can be selected for one of two functions:
1: Pulse signal 0-1000 c/s. The signal can for instance be taken to a counter for volume registration. The signal can also be used for registration of actual flow.
2: Current signal 4-20mA (only for transmitter in extended version). The signal can be taken to a regulator for controlling the liquid flow.

Besides these three outputs it is possible to connect the flow transmitter direct to the display unit PD 210. It is also possible to connect the extended version transmitter to a communication system for data processing.
 
DISPLAY UNIT
Introduction:
The display unit PD 210 can be connected direct to the transmitter. The display unit can be used as an accumulative counter and pre-set counter and for the registration of instantaneous values of flow rate and temperature. The display unit is also used in connection with fault finding.
 
Functions:
Accumulative Counter: The display unit registers the total volume, e.g. in m3.
Pre-set Counter: Before commencing measurement a SET-point is inserted, and the pre-set counter is reset manually. When the required volume is achieved, OUTPUT 2 gives a stop signal.
Instantaneous value, flow: The display unit registers the actual flow rate, e.g. in m3/h.
Instantaneous value, temperature: The display unit registers the actual temperature in ¢XC.
Fault finding: The flow transmitter is equipped with a comprehensive test system which is able to disclose faults, arising from improper use of the transmitter, or faults arising from the transmitter during use. When the test system registers a fault, an >>A<< appears in the first digit of the display. By pressing the >>TEST<< button the display will register an error checking code of two digits, registering the type of error.

Connection:
The display unit is connected to the flow transmitter with one double-connector cable. The display unit is supplied with power via this cable. It also transmits the exchange of data between the flow transmitter and the display unit. The length of the cable must not exceed 100 m.

Location:
The display unit is intended for fixed installation e.g. in a panel. The unit is waterproof. The ambient temperature
limits are - 10¢XC to + 50¢XC.
 
Dimensions:
 
Table 1: Dimensions - Standard-calibration
 
D
 
 
Stand-calibration
 
nom. size
Capacity
Weight
OUTPUT 2
OUTPUT 3
Size
mm
m3/h
Kg
l/pulse
l/pulse
C25
25
8
5
1,00
0.01
C38
38
20
5
1,00
0.01
C51
51
40
5
10,0
0.1
C63
63.5
80
5
10,0
0.1
 
ORDERING
Flow transmitter:
The dimension and data of the transmitter are indicated by an order number as shown in the example below:
 
 
*If current output on OUTPUT 3 is required instead of pulse-output this must be stated in writing below the order number.
  Furthermore, the flow at which full signal (20mA) is required on the current output should be stated.
  Example: Current output 20mA at 30,000 L/h.
 
Display unit:
Example:
 
Clamp set:
Example:
   
The clamp set consists of:
2 clamp rings
2 clamp liners
2 gaskets for above