| SPECIFICATIONS |
Accuracy
Under Surrounding
Temperature 25 ¡Ó 5¢J |
| Thermocouple |
:
K, J, E, T, R, S (Set Value +/- 0.3 or +/-
2¢J, whichever is greater) +/- 1 Digit |
| Thermocouple |
:
B (Set Value +/- 0.3 or +/- 3¢J, whichever
is greater) +/- 1 Digit |
| |
(B
input 0~500¢J is outside Guranteed Accuracy
range) |
| RTD |
:
(Set Value +/- 0.3 or +/- 0.8¢J, whichever
is greater) +/- 1 Digit |
| Voltage-Current |
:
( +/- 0.3% of Scalling Width or +/- 1 Digit,
whichever is greater) +/- 1 Digit |
|
| Input |
| Thermocouple |
:
K, J, E, T, R, S (JIS, IEC, DIN Standard)
B |
| RTD |
:
Pt100£[ (JIS, IEC, DIN Standard) , JPt100£[
(Old
) |
| Linear
Input |
:
DC1~5V, DC4~20mA |
|
| Output |
| Relay
Connection Output |
:
1a Connection (2A/250VAC, 2A/300VDC¡NCOS
£X=1) |
| SSR
Drive Voltage |
:
DC12V (Standard Value) Load Resistance not
less than 300£[ |
| Current
Output |
:
4~20mA Load Resistance not more
than 400£[ 740 (Standard Value)
Resolution |
|
| Control
System |
PID
Auto tuning, On/Off Control
Proportional Band (PB) = 0~200% of Thermperature
range, Integral Time ( l ) = 0~3999 Sec
Derivative Time (D) = 0~3999 Sec Proportional
Time (PT) = 0.5~64 Sec
Anti Reset Windup (ARW) = PB 1~100% of PB
On/Off Sensitivity (DIF) = 0.1~99.9¢J or
1~99¢J |
| Sampling
Time |
500ms |
Temperature
Range
*Accuracy is out of range when R and S are not
more than 99¢J(210¢K) or B is not more than 499¢J(930¢K)
|
| K
: -100~1200¢J (-148~2192¢K) |
B
: 0~1800¢J (32~3272¢K) |
| E
: -200~1000¢J (-328~1832¢K) |
S
: 0~1600¢J (32~2912¢K) |
| J
: -100~800¢J (-148~1472¢K) |
| C |
:
-200~500¢J (-328~932¢K) |
| |
-199.9~500.0¢J (-199.9~932.0¢K) |
|
| T
: -150~300¢J (-238~572¢K) |
| R
: 0~1600¢J (32~2912¢K) |
| G |
:
-200~850¢J (-328~1562¢K) |
| |
-199.9~850.0¢J (-199.9~1562.0¢K) |
|
|
| Alarm
Function |
Max
3 point (1a X 2 point, 1c X 1 point) 32 type temperature
alarm
Choose from Sensor/Heater Abnormal Alarm (Heater
Current Display Function included) |
| Communication
Function |
Compatible
with RS-485 signal format |
| EEPROM |
1
million times / cell rewritable |
| Voltage
Power Supply |
Free
Power AC100~240V -15%, +10% 50/60Hz
|
| Operating
Temperature |
-10~60¢J
(Assuming no dew drop condensation)
|
| Storage
Temperature |
-20~70¢J
(Assuming no dew drop condensation)
|
| Operating
Humidity |
R
H 35~85 %
(Assuming no dew drop condensation)
|
| Power
Consuption |
not
more than 12VA |
| Dielectric
Resistance |
not
less than 100M£[, D C 500V, Between Output relay
terminals and power supply terminals |
| High
Potencial Rating |
A
C 2300V for 1 Min, Between Output relay terminals
and power supply terminals |
| Earthquake-proof |
1-~55Hz,
All Ampritude 0.3mm Each X,
Y, Z Direction for 1 hour |
| Shock
Proof |
5
times 196 m/s2
(20G) to X, Y, Z each direction |
| Weight |
About
200g (Only main component) |
| Standard |
Safety
: EN61010-1 EMC : EN61326 |
| Structure
/ Material |
Water
Proof Front Panel IP64 / Case : ABS (UL94V-2) |